综合久久影院-综合久久伊人-综合久久一区二区三区-综合久久五月天-亚洲欧美日韩国产一区图片-亚洲欧美日韩国产一区二区三区精品

Muen
News

News

Enterprise service provider

location : Home > News > Technical information

The reason and check method of inverter low voltage and overload trip

2023-05-20 12:17:11

Reasons for inverter low voltage trip


1. The low voltage of the inverter mainly refers to the low voltage of the intermediate DC circuit. Generally, the reason for the low voltage of the intermediate DC circuit comes from two aspects:


(1) Low voltage from the power input side


Under normal circumstances, the power supply voltage is 380V, and the allowable error is -15%~10%. After three-phase bridge full-wave rectification, the intermediate DC voltage value is 513V. In some cases, the power line voltage is small and the voltage fluctuation will not be The low voltage trip of the inverter will only cause the inverter to operate if the effective value of the grid voltage is between 80% and 85% of the rated value and the duration exceeds one cycle. The low voltage on the input side of the power supply is mainly due to the fluctuation of the grid voltage or the switching of the main power line, the power supply sine wave amplitude is affected by the lightning strike, the transformer of the power plant itself is overloaded or the load is unbalanced, etc.


(2) Low voltage from the load side


The reasons for this are mainly the start-up and application of large equipment, line overload, or starting large motors. The frequency converter is composed of rectifier and inverter. Through the research of the inverter, the low voltage of the inverter refers to the low voltage of the middle DC loop (that is, the input voltage of the inverter is too low). General frequency converters have protection functions of overvoltage, loss of voltage and instantaneous power failure. The inverter device of the inverter is divided into GTR and IGBT. When the inverter device of the inverter is GTR, once the voltage is lost or the power is cut off, the control circuit will stop outputting the signal to the drive circuit, so that the drive circuit and GTR all stop working, the motor It will be in free braking state. When the inverter device is IGBT, after the voltage loss or power failure, the inverter will be allowed to continue to work for a short time td. If the voltage loss or power failure time is totd, the inverter will protect itself and stop running. Generally, td is between 15 and 25 ms, and the power supply “shaking” time is generally more than a few seconds. The inverter will protect itself and stop running, so that the motor stops. Therefore, to solve the problem of inverter low voltage trip can not start from the inverter's inherent time td and voltage loss time to, but must start from the amplitude of the voltage drop.


2. Solutions for inverter low voltage trip:


There are two key points to be solved to solve the problem of inverter low voltage trip:


(1) It is necessary to select the inverter with IGBT inverter device;


(2) It is necessary to select the inverter that can still work normally under the condition of large voltage loss.


The motor can rotate, but the running current exceeds the rated value, which is called overload. The basic reflection of overload is that although the current exceeds the rated value, the magnitude of the excess is not large, and generally a large inrush current is not formed.


The reason and inspection method of inverter overload trip


1. The main reason for inverter overload


(1) Malfunction, the current detection part inside the inverter fails, and the detected current signal is too large, causing a trip.


(2) The mechanical load is too heavy. The main feature of the heavy load is that the motor heats up and can be found by reading the running current from the display.


(3) The three-phase voltage is unbalanced, which causes the operating current of a certain phase to be too large, resulting in overload tripping. It is characterized by unbalanced motor heating, which may not be found when the operating current is read from the display (because the display only shows one Phase current).


2. Check method of whether the inverter is overloaded


(1) Check whether the three-phase voltage on the motor side is balanced. If the three-phase voltage on the motor side is unbalanced, then check whether the three-phase voltage on the output side of the inverter is balanced. If it is not balanced, the problem is within the inverter.


If the voltage at the output of the inverter is balanced, the problem lies in the line from the inverter to the motor. Check whether the screws of all terminals are tightened. If there is a contactor or other electrical appliances between the inverter and the motor, It should be checked whether the terminals of the related electrical appliances have been tightened and the contact conditions of the contacts are good.


If the three-phase voltage on the motor side is balanced, you should understand the operating frequency at the time of tripping: if the operating frequency is low and vector control (or no vector control) is not used, first reduce the U/f ratio, if it can still drive the load , It means that the original preset U/f ratio is too high, the peak value of the excitation current is too large, and the current can be reduced by reducing the U/f ratio;


If the load can not be moved after the reduction, you should consider increasing the capacity of the inverter; if the inverter has vector control function, the vector control method should be used.


(2) Check whether the motor heats up. If the temperature rise of the motor is not high, first check whether the electronic thermal protection function of the inverter is preset properly. If the inverter still has a margin, the preheating of the electronic thermal protection function should be relaxed. Set value.


If the temperature rise of the motor is too high, and the overload is normal overload, it means that the motor is overloaded. At this time, whether the transmission ratio should be properly increased to reduce the load on the motor shaft. If it can be increased, increase the transmission ratio. If the transmission ratio cannot be increased, the capacity of the motor should be increased.


General purpose frequency converter


label

QR code

The public,

Mobile station
The public, Mobile station

Contact

未標(biāo)題-8.png 0755-81719517
未標(biāo)題-10.png0755-81719530 未標(biāo)題-11.png[email protected]
未標(biāo)題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

Navigation

Home          About

Product      Case

Solution      Service

Job      News

Contact          

Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號(hào):粵ICP備12045920號(hào)
主站蜘蛛池模板: 国产在线每日更新 | 狠狠操社区 | 岛国成人 | 视频一区二区三区自拍 | 一级特黄aaa大片在线观看 | 岛国片在线 | 国产一级毛片高清视频在线 | 亚洲区一二三四区2021 | 亚洲国产成人精品激情 | 手机国产看片 | 久久精品亚洲一级毛片 | 国产精品一区不卡 | 国产精品福利网站 | www精品一区二区三区四区 | 亚洲天天更新 | 天天摸日日摸 | 亚洲一级毛片免费在线观看 | 欧美性色黄大片在线观看 | 亚洲天堂在线视频播放 | 日本免费成人网 | 成人三级在线 | 久久丁香视频 | 午夜资源网 | 亚洲日韩中文字幕一区 | 亚洲欧美日韩中文综合v日本 | 麻豆导航 | 欧美青青草 | h在线看免费视频网站男男 h在线看 | 精品国产高清a毛片无毒不卡 | 国产成人精品亚洲一区 | 免费国产97久久青草 | 欧美一二三区 | 麻豆影片| 国产在亚洲线视频观看 | 天天操天天插 | 日本一区二区三区四区不卡 | 99精品国产第一福利网站 | 色视频在线观看视频 | 日本在线高清版卡免v | 97视频免费在线观看 | 高清xx另类麻豆性色生活片 |