综合久久影院-综合久久伊人-综合久久一区二区三区-综合久久五月天-亚洲欧美日韩国产一区图片-亚洲欧美日韩国产一区二区三区精品

Muen
News

News

Enterprise service provider

location : Home > News > Technical information

Use your inverter with the right power

2023-05-20 13:07:17

Low voltage fault


The VFD reports a low voltage fault when the DC link voltage of the drive drops below 62% of the nominal level at the high setting (480 VAC) and 50% of the nominal value of the low setting (400 VAC).


The + 10% and - 15% voltage tolerances in most manuals are recommended operating ranges to allow the driver on hand to maintain high efficiency and proper motor current. The drive can be below these tolerances, but the reduced voltage can have unpredictable effects on motor current, motor temperature and overall performance.


More specifically, if the line voltage parameter of the driver is set to high and 480 VAC is being applied, the driver will generate a low voltage fault when the DC link voltage drops to 62% of the nominal - e.g., 480 VAC · 0.62 · √ 2 = 421 VDC. The nominal DC link voltage is 480 VAC · √ 2 = 679 VDC.


Notes on switching


Although it is generally accepted to switch VFD from line supply to standby generator in many applications, there are some limitations. Most importantly, the phase to phase voltage input voltage swing of many portable standby generators is greater than the phase to phase voltage tolerance recommended by the driver, usually less than 2%. To prevent voltage oscillations, VFDs are equipped with surge protectors in the input rectifier circuits - but external protection (e.g. surge arresters) may be required for severe input disturbances. Large variance will produce large ripple on DC bus capacitance, which will cause capacitor and other power components to be damaged over time.


Another potential problem arises when switching from line power to standby generators. Most drivers take at least two minutes to power up again; failure to follow this guideline may damage the charging relay circuit, or at least damage the input fuse or trip the circuit breaker.


3% line reactor may improve the current surge caused by moderate input power voltage.


Another solution is to add a voltage monitor with an appropriate time delay. They have protection trip levels to shut down the drive in the event of under voltage, over voltage, loss of phase and phase to phase voltage imbalance. These devices ensure that the VFD is not exposed to unbalanced input power or power up until the voltage is within tolerance and the appropriate delay time is met.


Isolation transformer


The final recommendation - the most expensive solution - is to use isolation transformers. This ensures complete isolation of input power issues associated with grounding and noise that may affect the drive. Does isolation transformer provide better protection than line reactor? Yes. When does the application need isolation transformer? This type of transformer is recommended when installed close to the substation.


There are many advantages in inserting driver isolation transformer between VFD and its power supply. Isolation ensures that there is no direct electrical connection between the source and the load - but for any transformer other than an autotransformer. The unique feature of the drive isolation transformer is the grounding electrostatic (Faraday) shield placed between and around the primary and secondary windings. This shielding reduces the capacitance coupling involved in the transmission of common mode voltage interference by one million times. Without this shielding, the capacitor allows high frequency noise and transient voltage spikes to pass through the transformer.


Common mode transients are transients that occur between the ground and the neutral point of an AC system. Although the two parts of a circuit are usually combined at one point, they cannot be considered to have the same potential throughout the power system. The common mode transient interference results from the normal operation of switching power supply, driver operation, arc welding machine, lightning, and even stepping motor. Some isolation transformers also prevent "normal mode" transients between the line and neutral.


Consider an application in which the daily utility power supply of a substation capacitor bank in an industrial park causes a transient voltage spike - amplified by reflection of field capacitors in a nearby factory. Suppose a facility in the park has several small drives rated at 7.5 HP. Normal mode transients can cause these drives to shut themselves down, resulting in costly process downtime. This interruption can be prevented by isolating the transformer.


Frequency converter manufacturer


label

QR code

The public,

Mobile station
The public, Mobile station

Contact

未標(biāo)題-8.png 0755-81719517
未標(biāo)題-10.png0755-81719530 未標(biāo)題-11.pngamb@ambition.com.cn
未標(biāo)題-12.pngFloor 1, 5 and 6, building 7, lijincheng science and technology industrial park, gongye dong road, longhua new district, shenzhen

Navigation

Home          About

Product      Case

Solution      Service

Job      News

Contact          

Copyright © Shenzhen Ambition Electronic Co., Ltd Record number:備案號:粵ICP備12045920號
主站蜘蛛池模板: 日本高清在线精品一区二区三区 | 看黄网站在线播放| 香蕉在线观看| 国产精品日本不卡一区二区| 青草综合| 91精品国产91久久久久| 久久久久综合给合狠狠狠| 五月婷婷激情综合网| 国产精品成人一区二区| 清纯唯美亚洲综合激情| 91好色| 久热亚洲| 亚洲乱码视频在线观看| 国产亚洲高清在线精品不卡| 日韩欧美一区二区久久| www操操操| 欧美黑人巨大xxxxxx视频| 愉拍自拍视频在线播放| 精品欧美一区二区三区在线观看| 特级a级毛片| 国产成人综合亚洲亚洲欧美| 青青操青青操| 91视频这里只有精品| 免费jjzz在线播放国产| 亚洲日本黄色| 黑人视频网站| 四虎影院官网| 国产福利一区二区在线观看| 轻轻草在线视频| 99精品视频在线观看免费| 免费观看黄页网站| 夜夜夜操操操| 精品视频入口| 西人人体韩国makemodel| 国产精自产拍久久久久久| 日韩精品中文字幕视频一区| 99视频在线观看视频| 欧美成人黄色片| 在线免费看毛片| 久久精品国内偷自一区| 亚洲国产一区二区三区在线观看|